The APC Symmetra PX 200kW is a world class, redundant, scalable, 3 Phase UPS power protection system designed to cost effectively provide high levels of availability. Seamlessly integrating into today’s state-of-the-art data center designs, the Symmetra PX is a true modular system. Made up of dedicated and redundant modules–power, intelligence, battery and bypass, all engineered into a design that is easily and efficiently serviceable, this architecture can scale power and runtime as demand grows or as higher levels of availability are required. Symmetra PX serves as the core power train that drives APC InfraStruXure systems for small and medium data centers but can also power individual “zones” of larger data centers. Highly manageable, the Symmetra PX features self-diagnostic capabilities and standardized modules which mitigate the risk of human error resulting in increased overall data center reliability.requirements. The specification below are for a 200 kVA / kW configuration.
Output
• Output Power Capacity- 200.0 KWatts / 200.0 kVA
• Max Configurable Power- 500.0 KWatts / 500.0 kVA
• Nominal Output Voltage- 400V 3PH , 480V 3PH
• Output Voltage Distortion- Less than 2%
• Output Frequency (sync to mains)- 50 Hz, 60 Hz
• Output Frequency (not synced)- 60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal
• Other Output Voltages- 415
• Load Crest Factor- Unlimited
• Topology- Double Conversion Online
• Waveform Type- Sine wave
• Overload Operation- 10 minutes @ 125% and 60 seconds @ 150%
• Output Connections- (1) Hard Wire 4-wire (3PH + G) (Battery Backup),, (1) Hard Wire 5-wire (3PH + N + G) (Battery Backup)
• Output Voltage THD- < 2% linear load and <3% non-linear load
• Transfer Time- 2ms typical
• Bypass- Built-in Static Bypass
Input
• Nominal Input Voltage- 400V 3PH , 480V 3PH
• Input Frequency- 40 – 70 Hz (auto sensing)
• Input Connections- Hard Wire 4-wire (3PH + G), Hard Wire 5-wire (3PH + N + G)
• Input voltage range for main operations- 340 – 460 (400V), 408 – 552 (480) V
• Input Total Harmonic Distortion- Less than 5% for full load
• Type of Input Protection Required- 3-pole breaker
• Maximum Short Circuit Withstand (Icw)- 50.0 kAmps
• Input Power Factor at Full Load 0.99
Batteries
• Battery type- VRLA
• Typical recharge time- 3.5 hour(s)
• Battery Volt-Amp-Hour Capacity- 67392
• Extendable Run Time- 1
• Extended Run Options- APC-Symmetra-PX-200kW-Scalable-to-250kW-without-Maintenance-Bypass-or-Distribution-Parallel-Capable
• Efficiency in Battery Operation- 96.5 %
• Overload Operation- 10 minutes @ 125% and 60 seconds @ 150%
Communications & Management
• Interface Port(s)- SYPX250-500_Parallel
• Pre-Installed SmartSlot™ Cards- AP9635CH
• Control panel- Touch Screen LCD User Interface
• Emergency Power Off (EPO)- Optional
• Available SmartSlot™ Interface Quantity- 3
Physical
• Maximum Height – 78.39 inches ( 1991 mm , 199.1 cm )
• Maximum Width – 106.3 inches ( 2700 mm , 270.0 cm )
• Maximum Depth – 42.13 inches ( 1070 mm , 107.0 cm )
• Net Weight – 8199.4 lbs. ( 3727.0 kg )
• Shipping weight- 9046.4 lbs. ( 4112.0 kg )
• Shipping Height- 84.65 inches ( 2150 mm , 215.0 cm )
• Shipping Width- 161.81 inches ( 4110 mm , 411.0 cm )
• Shipping Depth- 50.0 inches ( 1270 mm , 127.0 cm )
• Color- Black
Environmental
• Operating Temperature- 32 – 104 °F ( 0 – 40 °C )
• Operating Relative Humidity- 0 – 95 %
• Operating Elevation- 0-3333 ft ( 0-999.9 meters )
• Storage Temperature- -15 – 40 °C
• Storage Relative Humidity- 0 – 95 %
• Storage Elevation- 0-50000 ft ( 0-15000 meters )
• Audible noise at 1 meter from surface of unit- 54.0 dBA
• Online Thermal Dissipation- 24757.0 BTU/hr
• Protection Class- NEMA 1, IP 20